Since it's inception
in 1964, the pre-pressurized potable water tank has assumed various designs
and has proven useful in a wide variety of open-system applications. Originally
used in well installations, this technology gained widespread acceptance and
was soon applied in a variety of applications requiring pressurized water storage.
With this flexibility, however, can come confusion as to installation scenarios
and related sizing. Below, we'll take a look at proper use and related sizing
techniques in such applications as pump cycle control, volume maintenance, and
water treatment systems.
Common to the below
examples is the fact that it is necessary to determine both the amount of tank
storage needed and the pressures necessary to obtain that storage. Simply stated:
All sizings use the same principle with different values. Referred to as Boyle's
Law of Ideal Gases, this principle will be used to determine how much water
is stored in tank at a given pressure. This multiplier will be referred to as
the Acceptance Factor. Keep this equation in mind as a foundation to size any
pre-pressurized tank:
Pump Systems
It is common knowledge in the water systems industry that cycling a pump motor
rapidly will often lead to failure. To prevent this, most pump manufacturers
normally recommend a minimum pump runtime. In order to achieve the runtime,
the pre-pressurized tank must store a given volume of water between pump cycles.
Doing so requires the pump to run for a specific period to fill the tank. In
general, larger pumps require longer intervals between start cycles. When sizing
a pre-pressurized tank for the above purpose, the following information should
be known: Pump horsepower (determines runtime), pump output in gallons per minute
(GPM), and pressure switch setting in psi (cut-in & cut-out). The below
procedure will guide you through a sizing scenario using a 1hp pump. The pump
will be operating at 15 GPM with a pressure switch setting of 40psi cut-in and
60psi cut-out. The Acceptance Factors have already been calculated in the chart
provided. The figures are based on a tank precharge (initial air charge) set
2psi below pump cut-in pressure.
According to the "Recommended Minimum Runtime" notation, a 1hp pump
should operate for a period of at least 2 minutes between motor starts. In order
to run a 15GPM pump for 2 minutes, 30 gallons of storage is necessary. The Acceptance
Factor indicates that 27% of a given tank's volume will be usable water between
40 and 60psi. Dividing 30 by an acceptance factor of .27 results in a tank with
a volume of 111 gallons.
Volume Assist
Often, a plumbing system's flow requirements are not satisfied for any number
of reasons. Insufficient line size, unforeseen fixture additions, excessive
peak demand, and various types of line restriction all affect water flow capability
and/or requirements. If a given water line or pump is incapable of supplying
the necessary volume a system needs, pressure will suffer under flow conditions.
A pre-pressurized tank can be used to store water under pressure to assist in
meeting the above demands. Let's take a look at a common problem involving insufficient
line size and a bank of flush valves: Four 1.6 gallon per flush (GPF) flushometer-type
valves are installed on a ¾" water line with a static pressure of
50psi. In this example, the possibility exists for all four to be operated simultaneously.
Assuming the valves need 30psi to operate properly, what size tank is necessary
to satisfy this peak demand?
As shown, the tank
should be located centrally in reference to the fixtures. This will help prevent
flow imbalance due to uneven pressure drop. It is necessary to set the tank
air charge to the minimum pressure required by the fixtures. In this case, 30psi.
A check valve will also need to be installed prior to the bank of fixtures to
hold the pressurized water in the tank.
Reverse Osmosis
Pressurized storage is necessary in reverse osmosis systems due to the fact
that this type of filtration yields filtered water at a very slow rate. Using
a basic RO setup for reference, we'll explore the sizing principles involved.
Because of the minimal pressure requirement at the RO faucet, it is possible
to take advantage of a low tank precharge pressure to obtain a large storage
of pressurized water. In this example utilizing a 14 gallon tank, we'll assume
a 60psi feed pressure from the house, and an RO system that closes feed flow
when the storage tank pressure is 2/3 that of the feed line. Using the provided
charts, it is possible to determine the volume of usable water in the tank when
the feed shuts off.
It should be noted
that tank precharge affects the RO faucet outlet pressure. Although this requirement
is relatively low, it is important to take into consideration any pressure drops
between the tank and the faucet. The addition of an in-line post filter combined
with the slight elevation increase will decrease available pressure at the faucet.
As the above three
sizing scenarios have shown, choosing a pre-pressurized tank for a job need
not be guesswork. Provided the right information is available and applied correctly,
one equation will cover any sizing necessary. Knowing which data to gather and
how it relates to Boyle's Law will allow you to determine the correct tank size
for any application.
|